User Guide
5
Appendix A
40
Siemens Industry, Inc.
A6V11544782
02/22/2019
NOTE:
Ethernet port for XML connection is internal to the WSG unit. Remove the cover to
access Ethernet port. The enclosure has a notch in the side wall to seat the Ethernet
cable so the lid can be re-attached.
Data Array
Description
DA_STATUS
Array containing the below info
- Offset 0
Communication channel of system
- Offset 1
Communication network ID of system
- Offset 2
Number of sensors active in system
- Offset 3
Number of sensors that are sending a low battery signal
- Offset 4
1 means gateway is set as a repeater
- Offset 5
Value (minutes) of timeout setting; mode disabled if 0
- Offset 6
Number of sensors currently in timeout, if mode enabled
- Offset 7
Version of gateway software
DA_PWR
Battery voltage, or RSSI of RF powered sensors
DA_SECS
Time (seconds) since the last packet was received
DA_S1
Sensor input 1
DA_S2
Sensor input 2
DA_S3
Sensor input 3
DA_S4
Sensor input 4
DA_S5
Sensor input 5
DA_S6
Sensor input 6
DA_S7
Sensor input 7
DA_S8
Sensor input 8
DA_TXID
Transmitter ID (only valid in RF powered sensors)