User Guide

Software Installation and Commissioning
2
Building Automation System Gateway
17
Siemens Industry, Inc.
3. Select Setup then Save Setup. Do NOT change the File name, keep the default
TERATERM. This will save the above settings so they don’t need to be re-entered
the next time you use Tera Term.
4. Now that Tera Term is configured, press any key until you see the Gateway options
menu.
Building Automation System Gateway
The gateway is the device that receives data from the wireless sensor nodes and
interfaces to a BAS through industry standard protocols. The gateway is also used to
configure the sensor nodes prior to deployment.
The WSG has integrated mounting flanges and can be mounted to surfaces such as
wood or drywall with appropriate screws. Avoid mounting the gateway directly to a
metal surface as this can affect wireless reception. If mounting on a metal surface is
the only option, it is recommended to insert non-metallic material of at least 1/4”
between the gateway and metal surface to create a stand-off distance. The gateway