Data Sheet for Product

Page 4 of 5 Siemens Industry, Inc.
Specifications
General
Radio: 915MHz, internal antenna
Regulatory Approvals: FCC Part 15 and Industry Canada
Contains FCC ID: OA3MRF89XAM9A
Contains IC: 7693A-89XAM9A
Transmit Range: 300 ft. indoors to Gateway/Repeater in a typical commercial office building
Mounting: Wall mount, vertical, indoors
Gateway/Repeater
Power: 24 Vac/dc
Configuration Ports:
USB Type B PC Interface
USB Type A Sensor Interface
Network Port (Gateway): Ethernet, RS-485 or FTT-10
Temperature Sensor
Measuring Range: 50° to 90°F
Accuracy: ± 1°F (50-90°F)
Two Remote Sensor Inputs: 10k Ω Type 2 thermistor
Transmitted Data:
Node ID
Sensor readings
Battery voltage
Transmission Interval: Once per minute (non-configurable)
Expected Battery Life: 25 years
Temperature + RH Sensor
Measuring Range:
Temperature: 50° to 90°F
Humidity: 10 to 90%
Dew Point: 50° to 90°F
Accuracy:
Temperature: ± 1°F (50 to 90°F)
Humidity: ± 3% (10 to 90% rh)
Dew Point: ± 4% (50-90°F, 10-90% rh)
Transmitted Data:
Node ID
Sensor readings
Battery voltage
Transmission Interval: Once per minute (non-configurable)
Expected Battery Life: 25 years
Contact Closure Transmitter
Transmitted Data:
Contact status (OPEN/CLOSED), Qty:2
Node ID
Battery voltage
Transmission Interval: Per contact change, not to exceed once every 5 seconds.
Expected Battery Life: 25 years (Based on 1-minute transmission intervals. Shorter
intervals will decrease battery life. (Not for use as pulse counter.)
CO2 Sensor
Measuring Range: 0 to 5000 ppm CO2
Accuracy: +/- 50ppm +3% of the reading
Transmitted Data:
Node ID
Sensor readings
Battery voltage
Transmission Interval: Selectable, 1-5 minutes (Default = 4)
Expected Battery Life: 15 years (based on 4-minute transmission intervals)
Site Survey Tool
Simplifies process of determining number and location of repeaters
Measuring Range: -49 dB to -108dB
Matched pair of handheld devices