Data Sheet for Product

Technical Specification Sheet
Document No. 149-714
February 19, 2018
Siemens Industry, Inc. Page 1 of 2
Series QAA2200 Room Temperature Sensors
& Series QFA3200 Room Humidity Sensors
QxAx2xx.EWSN QxAx2xx.FWSN
Sensing Only Full HMI
Description
Series QAA2200 Room Temperature and Series
QFA3200 Room Humidity + Temperature sensors are
engineered to enable accurate and efficient control of
room comfort. A wide variety of output signals is
available for compatibly with nearly any control
system. The patented housing design seamlessly
blends into any décor and features strategically
placed ventilation slots to maximize airflow and
optimize accuracy.
The QFA3200 units combine a temperature sensor
with a relative humidity sensor in a single housing to
reduce installation time and improve overall room
aesthetics.
Installation is quick and straightforward with all
hardware included for mounting on a standard 2” × 4”
electrical box. Screws and anchors are provided for
mounting the sensor directly to a wall. Matching
gaskets and trim rings are also available.
The “Eversions have a blank front to prevent
unauthorized adjustments and are ideal for high traffic
areas or remote spaces that are not supervised.
The “F” versions feature a full HMI that can display
room conditions and temperature setpoint. The
display is easily configured to limit the information that
is available to the occupant. Temperature setpoint
can be adjusted using soft touch plus (+) and minus
(-) keys, and an override key enables the user to
manually signal to the controller that the space is
occupied.
Specifications
Temperature
Measuring range
Accuracy
1K Pt
1K (32°F) Ni
1K (70°F) Ni
10K Type II
10K Type III
100K Type II
4 to 20 mA/0 to 10V
32°F to 122°F (0°C to 50°C)
± 0.54°F (0.3°C) @ 32°F (0°C)
± 0.72°F (0.4°C) @ 32°F (0°C)
± 0.75°F (0.4°C) @ 75°F (24°C)
± 0.4°F (0.22°C) @ 77°F (25°C)
± 0.4°F (0.22°C) @ 77°F (25°C)
± 0.36°F (0.2°C) @ 77°F (25°C)
± 0.9°F (0.5°C)
Humidity
(QFA32xx only)
Measuring Range
Accuracy
Long-Term Stability
Resolution
Repeatability
0 to 100% rh
± 2% between 10 to 90%
<0.5% rh/year
0.03% rh
+/-0.1% rh
Setpoint/Override
(“F” versions only)
Setpoint Signal
QxAx2SS.FWSN
All others
Setpoint Range
Override Contact
4 to 20 mA or 0 to 10V/0 to 5V
0 to 10V/0 to 5V
55°F to 95°F (13°C to 35°C)
Momentary, 1A @ 24 Vac max.
Input Power
VA Rating
18 to 36 Vdc or 24 Vac ± 20%
1.5 VA, max.
Agency Listing
Color
Dimensions
Shipping Weight
UL 916
White
4.5” × 2.75” × 1.18”
(115 mm × 70 mm × 30 mm)
6 oz. (170 g)

Summary of content (2 pages)