Specifications, Continued
Humidity Specifications
Humidity Range
0% to 100% rh
Output Signal
Select 0-5V, 0-10V, 4-20 mA
Sensing Element Type
Digital Sensor IC (capacitive)
Humidity Accuracy
10% - 90% rh
± 2% rh
< 10% rh; > 90% rh
± 4% rh
Calibration Features
Temperature
Humidity
Adjustable to +/- 5°F
Adjustable to +/- 5% rh
Installation
NTC Types 100 ft. Maximum cable length.
6C #24 AWG, Belden
DFLEX3 or equal, NEC
Class 2
RTD Types 300 to 750 ft Maximum
cable length 18 to 22 AWG
twisted pair NEC Class 2
Installation Adjustments
None required
Cover
Dimensions 4.5" × 2.75" × 1.18"
(115 mm × 70 mm ×
30 mm)
Color
White
Weight
4 oz (0.11 kg)
Regulatory Agencies UL 916
Input Power 18 to 36 Vdc or
24 Vac ± 20%
VA Rating
1.5 VA, max.
Product Ordering Information
Description
Product Part Number
Humidity and Temperature Room Unit, 2%, RH: 0-10/0-5 Volt or 4-20 mA
selectable, 2% T: 10K Type 3 NTC, Display, Setpoint, Override, No Logo QFA3332.FWNN
Humidity and Temperature Room Unit, 2%, RH: 0-10/0-5 Volt or 4-20 mA
selectable, 2% T: 10K Type 2 NTC, Display, Setpoint, Override, No Logo QFA3330.FWNN
Humidity and Temperature Room Unit, 2%, RH: 0-10/0-5 Volt or 4-20 mA
selectable, 2% T: 1K Platinum (385) RTD, Display, Temp Setpoint, Override,
White, No Logo
QFA3312.FWNN
Humidity and Temperature Room Unit, 2%, RH: 0-10/0-5 Volt or 4-20 mA
selectable, 2% T: 1K Platinum (385) RTD, White, No Logo
QFA3312.EWNN
Humidity and Temperature Room Unit, 2%, 0-10/0-5 Volt or 4-20 mA selectable
outputs, Display, Temp Setpoint, Override, White, No Logo, No Comm Port
QFA33SS.FWNN
Humidity and Temperature Room Unit, 2%, 0-10/0-5 Volt or 4-20 mA selectable
outputs, White, No Logo
QFA33SS.EWNN
Accessories Ordering Information
Description
Product Part Number
Replacement Sensor Housing Base for QFA33xx.EWNN
563-102-03
Replacement Sensor Housing Base for QFA33xx.FWNN
563-102-04
Room Unit Back Plate (10-pack)
AQA2200-INTL
Room Unit Back Plate (Single)
AQA2200-2X4
Room Sensor Insulating Gasket (10-pack)
(Recommended for hollow wall installations.)
563-102 GSKT KIT