Basic Documentation
Table Of Contents
Configurations
DIP switch for configuration method selection
4
A6V12297475_en--_a
7 | 14
4 Configurations
4.1 DIP switch for configuration method selection
The sensor is a Modbus RTU (RS-485) slave device. It can be configured with a
Modbus master when DIP2-Position 7 is OFF (default setting).
The sensor has two sets of DIP switches: DIP1 and DIP2. It can be manually
configured with DIP switches when DIP2-Position 7 is ON.
For details, see DIP switch configuration [➙ 9].
4.2 Modbus configuration parameters
Name
Range/numeration
Default
Configurable
Modbus address
1...247
1
Baud rate (bps)
0 = Auto
1 = 9600
2 = 19200
3 = 38400
4 = 57600
5 = 76800
6 = 115200
0
Transmission format
(start bits-data bits-
parity-stop bits)
0 = 1-8-E-1
1 = 1-8-O-1
2 = 1-8-N-1
3 = 1-8-N-2
0
Bus configuration
command
0 = Ready
1 = Load
2 = Discard
0
Basic
Parity
Even
Odd
None
Even
Stop bits
1 / 2
1
Data
8 bits (0…255)
-
Identity
Slave
-
Cable length
< 600 m
-