Basic Documentation
Table Of Contents
Configurations
DIP switch configuration
4
10 | 14
A6V12297475_en--_a
The sensor has two sets of DIP switches: DIP1 and DIP2.
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Address
1
2
3
4
5
6
7
8
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
0
(default)
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
1
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
2
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
3
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
4
…
…
…
…
…
…
…
…
…
ON
ON
ON
ON
ON
ON
ON
ON
255
NOTES:
● Modbus address configuration: Valid address range 1…247, others = 0
● If an invalid address is set, the newly set values of register 764…768 are not
activated. The registers keep the previous value.
Baud rate
Parity
Stop bit
1)
Configuration
Function
1
2
3
4
5
6
7
OFF
OFF
OFF
0 = Auto
OFF
OFF
ON
1 = 9600
OFF
ON
OFF
2 = 19200
OFF
ON
ON
3 = 38400
ON
OFF
OFF
4 = 57600
ON
OFF
ON
5 = 76800
ON
ON
OFF
6 = 115200
ON
ON
ON
others = Auto
OFF
OFF
0 = Even (default)
OFF
ON
1 = Odd
ON
OFF
2 = No parity
ON
ON
others = Even
OFF
1 (default)
ON
2
OFF
Configurable via master
ON
DIP switches
DIP1
Address configuration
DIP2
Baud rate, transmission
format, configuration