Installation Instructions

Document No. 129-505
Installation Instructions
February 20, 2013
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and
models as design improvements are introduced. Products or company names mentioned herein may be the trademarks of their respective
owners. © 2013 Siemens Industry, Inc.
Siemens Industry, Inc.
Building Technologies Division
1000 Deerfield Parkway
Buffalo Grove, IL 60089
USA
+ 1 847-215-1000
Your feedback is important to us. If you have
comments about this document, please send them to
SBT_technical.editor.us.sbt@siemens.com
Drywall Mounting (No Rough-in),
Typical
CAUTION:
Over-tightening may cause the
sensor base plate to crack or bend.
8. Feed the extra field wiring cable back through
the hole in the sensor base plate.
9. Snap the sensor pieces together by hooking the
feet of the base plate into the slots on the front
plate, then pushing the top of the sensor until it
snaps into place.
10. Tighten the sensor front retaining screw (See
Figure 1).
The installation is now complete.
Wiring Diagram
2
1
3
4
5
6
7
8
9
Override DO
DC+
DC-
Passive Temp
0-10V or 4-20 mA Setpoint
0-10V or 4-20 mA Temp
0-10V or 4-20 R H
SEN0413R2
TOP
Figure 1. Drywall Mounting (No Rough-in), Typical.
1. Using the sensor base plate as a template, mark
the center field wiring hole and the mounting
hole locations (See Figure 1).
Table 1. Room Relative Humidity Sensors Installation,
0 to 10V or 4 to 20 mA.
NOTE: For drywall mounting, use only the top
and bottom holes.
Sensor Terminals Used
Available
Features
Power*
1 & 2
RH
9 & 2
Temp
8 & 2
Setpt
7 & 2
Ovrd
3 & 4
RH: Sensing only
RH: Sensing with
Display
– – –
RH and
temperature:
Sensing only
• •
RH and
temperature:
Sensing with
Display
• •
RH and
temperature: Full-
featured
• • • •
2. Drill two 3/16-inch (4.8 mm) mounting holes.
Insert two plastic wall anchors into the holes for
the mounting screws.
3. Cut a 1-inch (25 mm) center hole with a hole
saw.
4. Pull about 6 inches (150 mm) of the field wiring
cable through the hole in the wall and insert
through the back of the sensor base plate.
5. Secure the field wiring in the terminal block
located on the printed circuit board.
6. Push the field wiring cable through the hole in
the wall and loosely mount the sensor base
plate on the wall using the screws provided. Do
not tighten the screws.
* Power requirements for these devices is 20 to 30 Vdc.
NOTE:
The override and passive temperature outputs are
isolated circuits. To reduce wiring, you may jumper
pins 3 and 2 or pins 5 and 2; however, the inputs
on your controller must be referenced to the same
ground that is powering the sensor.
7. Level the sensor base plate for appearance and
then tighten the mounting screws.
Document No. 129-505
Printed in the USA
Page 2 of 2