Data Sheet for Product

5
Siemens
A6V11600411_en
--
_a
Smart Infrastructure 2019-08-07
Mode of operation
Relative humidity
The sensor acquires the relative humidity in the room via its capacitive humidity sensing
element whose electrical capacitance changes as a function of the relative humidity. The
electronic measuring circuit converts the sensor’s signal to a continuous DC 0...10 V or
4…20 mA signal, which corresponds to 0...100 % relative humidity.
Temperature
The sensor acquires the temperature in the room via its sensing element whose electrical
resistance changes as a function of the temperature.
This change in resistance is converted to an active DC 0…10 V or 4…20 mA output signal,
corresponding to a temperature range of 0…50 °C, –35…+35 °C, or –40...+70 °C. The
measuring range can be selected.
Disposal
The device is considered an electronic device for disposal in accordance
with the European Guidelines and may not be disposed of as domestic
garbage.
Dispose of the device through channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.