Data Sheet for Product
3
Siemens
Datasheet
A6V12046135_en--_a
Smart Infrastructure
2020-07-23
Cable routing and cable selection
Note that when routing cables, the longer the cable runs and the closer the cables, the
greater the electrical interference. Use shielded cables in EMC-prone environments.
Twisted pair cables are required for both secondary supply lines and signal lines.
Mounting
Location
Inner wall (not exterior!) in the room to be air conditioned; not in niches, not behind curtains,
not above or close to heat sources or shelves nor on walls with a chimney. Do not expose to
direct light from spot lights or direct solar radiation.
Install the sensor in the occupied space about 1.5 m above the floor and at least 50 cm from
the next wall.
Seal the end of the conduit at the sensor to prevent false measurements due to drafts
through the conduit.
Mounting instructions
Mounting instructions are enclosed in the package.
Chemical vapors
The sensor is a highly sensitive measuring device and must be handled with care. Exposure
to high concentrations of chemical vapors for longer periods may distort sensor readings.
NOTICE
Avoid direct contact with chemicals in any form. Do not touch sensitive components with
bare hands or tools as this will negatively impact measuring accuracy.
CAUTION! Do not to apply voltmeters or ohmmeters directly to the sensing element.
Commissioning
Sensor functions can be checked 30 minutes after applying power.
Disposal
The device is considered an electronic device for disposal in accordance
with the European Guidelines and may not be disposed of as domestic
garbage.
● Dispose of the device through channels provided for this purpose.
● Comply with all local and currently applicable laws and regulations.