Basic Documentation
Table Of Contents
Configuration
DIP switch configuration
4
A6V12045847_en--_a 9 | 14
● The register number starts at 1.
● The sensor rejects a command with an error notice in the event of a multiple-
writing command from the master with invalid values. The register values
remain unchanged.
● Software version format: Major version is 1 byte, minor version is 1 byte and
build version is 2 bytes, such as [2.01.33] = 0x02010021.
● Supports only the holding register.
4.4 DIP switch configuration
The Modbus setting can be configured via DIP switches ( DIP2-position 7 must be
set to ON).
NOTICE
●
Modbus registers 764…766 are not writable via a master under DIP switches
configuration.
● When DIP1-position 1...8 are set to 255 and DIP2-position 7 is ON, Modbus
parameters are reset to factory default settings: Only Modbus address, baud
rate and transmission format are reset to factory default.
The sensor has two sets of DIP switches: DIP1 and DIP2.
DIP1
Address configuration