Basic Documentation
Table Of Contents
Configuration
DIP switch to configure method selection
4
A6V12045847_en--_a 7 | 14
4 Configuration
4.1 DIP switch to configure method selection
The sensor is a Modbus RTU (RS-485) slave device and can be configured with a
Modbus master when DIP2-Position 7 is OFF (default setting).
The sensor has two sets of DIP switches: DIP1 and DIP2 and can be manually
configured with DIP switches when DIP2-Position 7 is ON.
For details, see DIP switch configuration [➙ 9].
4.2 Modbus configuration parameters
Name Range/numeration Default
Configurable Modbus address 1...247 1
Baud rate (bps) 0 = Auto
1 = 9600
2 = 19200
3 = 38400
4 = 57600
5 = 76800
6 = 115200
0
Transmission format
(start bits-data bits-
parity-stop bits)
0 = 1-8-E-1
1 = 1-8-O-1
2 = 1-8-N-1
3 = 1-8-N-2
0
Basic Parity Even
Odd
None
Even
Stop bits 1 / 2 1
Data 8 bits (0…255) -