Basic Documentation

Configuration
DIP switch configuration
4
10 | 14 A6V12045847_en--_a
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Address
1 2 3 4 5 6 7 8
OFF OFF OFF OFF OFF OFF OFF OFF 0
(default)
OFF OFF OFF OFF OFF OFF OFF ON 1
OFF OFF OFF OFF OFF OFF ON OFF 2
OFF OFF OFF OFF OFF OFF ON ON 3
OFF OFF OFF OFF OFF ON OFF OFF 4
ON ON ON ON ON ON ON ON 255
NOTES:
Modbus address configuration: Valid address range 1…247, others = 0
Newly set values of register 764…766 are not activated for an invalid address;
the registers retain the previous value.
Baud rate Parity Stop bit
1)
Configuration Function
1 2 3 4 5 6 7
OFF OFF OFF 0 = Auto
OFF OFF ON 1 = 9600
OFF ON OFF 2 = 19200
OFF ON ON 3 = 38400
ON OFF OFF 4 = 57600
ON OFF ON 5 = 76800
ON ON OFF 6 = 115200
ON ON ON others = Auto
OFF OFF 0 = Even (default)
OFF ON 1 = Odd
ON OFF 2 = No parity
ON ON others = Even
OFF 1 (default)
ON 2
OFF Configurable via master
ON DIP switches
NOTE:
1)
Parity + Stop bit only support the following combinations: 1-8-E-1, 1-8-O-1, 1-8-
N-1 and 1-8-N-2. Others will be treated as 1-8-E-1.
DIP2
Baud rate, transmission
format, configuration