Installation Instructions

Wiring
1
A6V11478123_en_c 7 | 22
1.4 Wiring
1.4.1 Electrical grounding
Note the following grounding situation of the QBM97.
QBM97 uses a non isolated RS485-Interface
The reference of RS485 transceiver is connected to GND
all GND pins are on the same potential
if the Climatix controller and QBM97 are connected to the same power source,
take care to avoid miswiring between 24 V input and GND
The document "Modbus communication" (J3960) provides profound information
on Modbus grounding.
Transformer
Power-
supply
24V
0V
REF B- A+
Earth
Sensor module
Not isolated RS485
M
Situation
Consequences