Data Sheet for Product
8
Siemens A6V11478118_en_c
Smart Infrastructure 2021-01-20
Limits
Tolerable overload on one side ● on Px +: 10000 Pa
● on Px -: 400 Pa
Rupture pressure ● at room temperature: 2x overload
● at 70 °C: 1.5x overload
Media / Admissible temperature Air and neutral gases / 0…70 °C
Maximal tube length 15 m
Data for volume flow calculation
Permitted k factor range 0...1500
Calculation formula
Measuring variables l/s, m
3
/h, m
3
/s
NOTICE
Accuracy of volume flow calculation
The accuracy of the volume flow calculation is proportional to the root of the pressure
measurement accuracy multiplied by the k-factor.
Additional data
Pressure connections ∅ 6,2 mm, (for pipe inside ∅ 5 mm)
Maintenance Maintenance free