Data Sheet for Product
5
Siemens A6V11478118_en_c
Smart Infrastructure 2021-01-20
Operating elements
PCB overview
ON
1 2 3 4 5 6 7 8 9
LED1
A
B
C
Element Description
A Status LED
B DIP switches
C Push button
Status LED indicator
Color Flash response Function
Red
Blinking, 1 second on, 5 seconds
off
● Internal error
Red
Blinking, 0.1 seconds on, 1 second
off
● Invalid configuration
Orange Continuous ● Waiting for on-event addressing
Orange
Blinking, 1 second on, 5 seconds
off
● Bus communication failure
Orange
Blinking, 0.1 seconds on, 1 second
off
● Device not configured (factory settings)
Green Continuous ● Start up
Green Blinking ● Normal operating mode
Green Flickering ● Bus communication
Blue Continuous ● Zero point reset
Workflows and 'How to in
structions' for the DIP switches and the push button can be found
in manual A6V11478123.
DIP switches
● Use DIP switches for adjustment of the Modbus address (DIPs 1 to 8) and for Modbus
line termination (DIP 9).
● The DIP switches have priority over register 'Modbus address'.
Push button
Duration of operation Function
5...10 s On-event addressing
10...20 s Zero point reset
20...30 s Reset to factory setting