Data Sheet for Product

5
Siemens A6V11478118_en_c
Smart Infrastructure 2021-01-20
Operating elements
PCB overview
ON
1 2 3 4 5 6 7 8 9
LED1
A
B
C
Element Description
A Status LED
B DIP switches
C Push button
Status LED indicator
Color Flash response Function
Red
Blinking, 1 second on, 5 seconds
off
Internal error
Red
Blinking, 0.1 seconds on, 1 second
off
Invalid configuration
Orange Continuous Waiting for on-event addressing
Orange
Blinking, 1 second on, 5 seconds
off
Bus communication failure
Orange
Blinking, 0.1 seconds on, 1 second
off
Device not configured (factory settings)
Green Continuous Start up
Green Blinking Normal operating mode
Green Flickering Bus communication
Blue Continuous Zero point reset
Workflows and 'How to in
structions' for the DIP switches and the push button can be found
in manual A6V11478123.
DIP switches
Use DIP switches for adjustment of the Modbus address (DIPs 1 to 8) and for Modbus
line termination (DIP 9).
The DIP switches have priority over register 'Modbus address'.
Push button
Duration of operation Function
5...10 s On-event addressing
10...20 s Zero point reset
20...30 s Reset to factory setting