Data Sheet for Product
10
Siemens A6V11478118_en_c
Smart Infrastructure 2021-01-20
Inputs and outputs
Analog inputs AI1, AI2
Type Range Accuracy Resolution TK/B
25/85
Pt1000 -50...+150 °C ±0.5 K 0.1 K 3850 ppm/K
LG-Ni1000 -40...+120 °C ±0.5 K 0.1 K 5000 ppm/K
NTC10k -40...-25 °C ±1.0 K 0.2 K 3979
-25...+75 °C ±0.5 K 0.1 K 3979
+75...+100 °C ±1.0 K 0.3 K 3979
+100...+125 °C ±3.0 K 1.0 K 3979
+125...+150 °C ±6.0 K 2.5 K 3979
Ni1000 -50...+150 °C ±0.5 K 0.1 K 6180 ppm/K
Input DC 0...10 V 0 V ±5 mV <5 mV -
5 V ±25 mV <5 mV -
10 V ± 50mV <5 mV -
Input resistance > 100 kΩ
NOTICE
Configuration: default settings of AI1 and AI2
● The configuration of AI1 and AI2 is done via application/HMI.
●
Default setting is "no sensor" (for details see "
Modbus registers [
➙
15
]
").
Analog outputs AO1, AO2
Type Voltage Resolution Accuracy
Output DC 0…10 V 0 V < 11 mV ±66 mV
5°V < 11 mV ±95 mV
10 V < 11 mV ±124 mV
● Output current: Maximum 1 mA (short-circuit proof)
● Minimal load: 10 kΩ
NOTICE
Configuration: default settings of AO1 and AO2
● The configuration of AO1 and AO2 is done via application/HMI.
● Default setting: AO1 shows pressure sensor1, AO2 shows pressure sensor2 (for details
see "
Modbus registers [
➙
15
]
").