Installation Instructions

Commission
ing
Addressing
2
A6V11478123_en_c 11 | 22
2 Commissioning
2.1 Addressing
2.1.1 DIP switches (Climatix and other controllers)
Use DIP switches for adjustment of the Modbus address and for termination.
The DIP-switches have priority over register 4x0764 (Modbus address).
The Modbus address (register 4x0764) is valid as soon as all DIP switches are
on '0'.
Changes of DIP switches are effective after 5 seconds.
Modbus addressing
The DIP switches allow addresses between 1…247 (Modbus specification).
The following example shows Modbus address '3':
Modbus termination
The termination is done with 120 Ω + 1nF.
Even if the addressing is done with "On-event addressing (Climatix controllers)
[ 12]", the termination has to be done manually.
1 2 3 4 5 6 7 8 9
1
2
1: On
0: Off
128 64 32 16 8 4 2 1
1 2 3 4 5 6 7 8 9
1
2
1: On
0: Off
128 64 32 16 8 4 2 1
1 2 3 4 5 6 7 8 92
1: On
0: Off