User Manual

Technical data
Electrical interface Power supply Safety extra low voltage (SELV, PELV)
QBM65.../C Supply voltage
Power consumption
Current draw
AC 24 V ±15 %, 50/60 Hz or DC 13.5...33 V
< 0.5 VA
< 10 mA
Output signal DC 0...10 V, R
Load
> 10 kΩ (not galvanically
separated, 3-wire connection, short-circuit-
proof, reversed polarity protection)
QBM75.../C
Supply voltage
Power consumption
Current draw
DC 11...33 V
< 0.7 VA
4...20 mA
Output signal
4...20 mA
,
R
Load
>
A0.02
V11voltage Operation
Ω
(2-wire connection, short-circuit-proof, re-
verse polarity protection)
Product data Measuring range See “Type summary”
Measuring element Piezoresistive (silicone-rubber diaphragm
and ceramic lever)
Measuring accuracy in correct mounting position
and at a room temperature of 25 °C
(FS = Full Scale)
QBM65-3/C
QBM65-10/C
QBM65-25/C
Zero point
Total, linearity, reproducibility, and hysteresis
TC zero point
TC sensitivity
<±0.7 % FS
<±1 % FS
<±0.05 % FS/°C
<±0.05 % FS/°C
QBM65-1/C
QBM75.1-1/C
Zero point <±1 % FS
Total, linearity reproducibility, and hysteresis
TC zero point
TC sensitivity
<±2 % FS
<±0.10 % FS/°C
<±0.06 % FS/°C
QBM75-1U/C Total, zero point, linearity, reproducibility, and
hysteresis
TC zero point
<±3 % FS (<±3 Pa)
<±0.10 % FS/°C
<±0.06 % FS/°C TC sensitivity
Long term stability ± 1 % FS to DIN IEC 60 770
Response time 90 % < 10 ms
Tolerable overload on one side
for ±
type
10 000 Pa
10 000 Pa on P1, 400 Pa on P2 or
-400 Pa on P1, -10 000 Pa on P2
Rupture pressure 2 × overload at room temperature
1.5 × overload at 70°C
Suitable media
Admissible temperature of medium
Air or non-aggressive gases
0...70 °C
Maintenance No maintenance required, recalibration rec-
ommended every 12 months
Protective data Degree of protection when mounted in
the recommended position
IP 54 to IEC 60 529
Safety class III to EN 60 730
Combustion class
Hin
ged cover
Pressure casing and housing
Plastic tubing
To UL94
HB
V-2
V-2
4/6
Siemens Differential pressure sensors QBM65…/C, QBM75…/C CA1N1919E
Building Technologies 27.08.2010