5
Smart Infrastructure
A6V11684000_en
--
_c
2021
-
02
24
Operating elements
PCB overview
Element Description
A Status LED
B DIP switches
C Button
Status LED indicator
Color Flashing Function
Red Blinking, 1 sec. on, 5 sec. off Internal error
Red
Blinking, 0.1 second on, 1 second
off
Invalid configuration
Orange Modulating Waiting for on-event addressing
Orange Blinking, 1 sec. on, 5 sec. off Bus communication failure
Orange
Blinking, 0.1 second on, 1 second
off
Device not configured (factory settings)
Green Modulating Start-up
Green Flashing Normal operation
Green Flickering Bus communication
Blue Modulating Zero point reset
Workflows and 'How to instructions' for the DIP switches and the push button can be
found in A6V11841988. See Section
Supplemental information [
11
]
.
DIP switches
Use DIP switches for adjustment of the Modbus address (DIPs 1 to 8) and for Modbus
line termination (DIP 9).
The DIP switches have priority over register 'Modbus address'.Button
Duration of operation Function
5...10 s On-event addressing
10...20 s Zero point reset
20...30 s Reset to factory setting
ON
123456789
LED1
A