Data Sheet for Product
Page 2 of 3
Siemens Industry, Inc.
Specifications
Electrical Data
Input power
Output signal
8 to 33 Vdc
4 to 20 mA
Short-circuit and polarity reversal
protected
Performance
Characteristics
Long-term stability
(Per DIN EN 60770)
Response time
Load cycle
1% Full Scale
10 ms
< 10 Hz
Resolution % Full Scale
0.25"
0.2
1"
0.1
2.5"
0.1
5" – 10"
0.1
Sum of linearity, hysteresis and
repeatability +/-% Full Scale
3.0%
1.0%
1.0%
0.6%
TC zero point typical +/-% FS/10K
0.2%
0.25
0.1%
0.1%
TC zero point max. +/-% FS/10K
1.0%
0.5%
0.4%
0.4%
TC sensitivity typical +/-% FS/10K
0.3%
0.2%
0.1%
0.1%
TC sensitivity max. +/- % FS/10K
0.6%
0.5%
0.5%
0.2%
Environmental Conditions
Suitable process media
Process/ambient temperature
Ambient storage temperature
Ambient humidity
Air and neutral gases
32°F to 160°F (0°C to 71°C)
14°F to 158°F (-10°C to 70°C)
Non-condensing
Installation Considerations
Enclosure
Electrical connections
Process connections
Mounting orientation
Maintenance requirements
NEMA 1
1/2" FNPT conduit
3/16" FNPT
Vertical or horizontal (condensation
must drain away from sensor)
None
Materials
Enclosure
Diaphragm
Measuring element
Polycarbonate
Silicone
Ceramic
Directives and Standards
FCC
Part 15 Subpart B Emissions
Environmental compatibility
Environmental product declaration
CE1E1922en provides information on
environmentally compatible product
design and assessment (RoHS
compliance, composition of substances,
packaging, environmental benefit, and
disposal).
ISO 14001 (environment)
ISO 9001 (quality)
SN 36350 (environ. compatible
products)
2011/65/EU (RoHS)