Data Sheet for Product
Accessories
AQB2002
Mounting kit for remote mounting with 1 m
copper capillary line, both ends prefabri-
cated ready for connection.
Thread adapters and terminal nuts made
of brass. Pressure connection with G1/8“
or G1/2“ outer threading.
Mounting instructions
Mounting instructions are enclosed with the differential pressure sensor.
The QBE63-DP... sensors can be connected directly with G
1
/8" or R
1
/8" screwed
fittings. Special precautions must be taken on site when mounting the sensors, to
ensure airtight screw connections.
• Use standard T-fittings or drill and de-bur measuring holes, each 5 mm diameter, for
the pressure tapping points (A).
• An isolating bypass (5) can be fitted to avoid overloading the pressure sensor on one
side while making adjustments.
• For inspection purposes, measuring circuits can be fitted with a measuring-T at the
sensor head.
Mounting for use with liquids:
• Always mount the sensor lower than the pressure measuring points
• Mount on a vibration-free surface
• Always evacuate the system
Supply Return
QBE...-DP...
P1
+
P2
–
2
2
3
3
4
4
1
1
A
A
+
–
5
ø max. 5 mm
90°
80357
4
Key:
A Measuring holes
1 Isolating valves
2 T-joints
3 Connection pieces (from mounting kit AQB2002)
4 Copper pipes (from mounting kit AQB2002)
5 Isolating bypass
For remote mounting, the sensor can be operated together with the AQB pressure
mounting kit in ambient temperatures of up to 70 °C for medium temperatures of up to
180 °C. Care must be taken in this case to ensure that the cooling efficiency of the
copper pipe is not reduced by additional heat sources or by restrictions to the air circu-
lation.
Disposal
The devices are considered electronics devices for disposal in term of European Di-
rective 2012/19/EU and may not be disposed of as domestic waste.
• Dispose of the device via the channels provided for this purpose.
• Comply with all local and currently applicable laws and regulations.
Recommended
measures:
Important note
Remote mounting
3/6
Siemens Differential pressure sensors QBE63-DP … CA1N1920E
Building Technologies 2014-07-30