Installation Instructions

Installation Instructions
Document No. 129-900
June 7, 2012
Wet Differential Pressure Sensor
with Manifold Assembly
Item Number 129-900, Rev. AA Page 1 of 3
Product Description
The Siemens Wet Differential Pressure Sensors utilize
a unique, well-proven ceramic technology making
them ideal for applications across a broad spectrum of
industries. These sensors are unidirectional with a
three-valve manifold.
Product Numbers
Product
Number
Burst
Pressure
on High
Side (psi)
Differential
Pressure
Rating (psi)
Differential
pmax.*
(psi)
QBE3190UD25
0 to 25 72
QBE3190UD50
0 to 50 116
QBE3190UD100
543
0 to 100 290
Pressure Rating
CAUTION:
The maximum manifold pressure rating
is 250 psi.
* Reference the sensors' pmax. rating.
Exceeding the recommended pressure
will damage the sensor.
Warning/Caution Notations
WARNING:
Personal injury/loss of life may
occur if you do not follow the
procedures as specified.
CAUTION:
Equipment damage/loss of
data may occur if you do not
follow the procedures as
specified.
Contents
Sensor/manifold assembly
Rubber gasket
Non-conduit assembly kit
Conduit cap
Required Tools
Thread sealant (Loctite 565 or equivalent)
(2) crescent wrenches: 1/2”, and 9/16”
Small, Phillips screwdriver
Small, flat-blade screwdriver
(2) 6-32 sheet metal screws or nylon tie wraps
Installation Time
30 minutes
Prerequisites
Use two male connector compression fittings
with 1/4”-18 NPT threads rated for system
pressure for the HIGH and LOW pressure
ports of the manifold.
Prepare the fittings with Loctite 565 Thread
Sealant or equivalent anaerobic liquid to
prevent leakage.
CAUTION:
Do not use putty, gasket-type material,
or tape.
Installation
Pressurizing the System
1. Before the system is pressurized ensure that:
a. Valves V1 and V2 are closed.
b. Valve V3 is open.
SEN0635R1
P1
V3
V1 V2
LOWHIGH
Figure 1. Sensor Flow Loop.