Installation Instructions

Installation Instructions
Document No. 129-901
July 3, 2012
Wet Differential Pressure Sensors
Item Number 129-901, Rev. BA Page 1 of 3
Product Description
The Siemens QBE Series Wet Differential Pressure
Sensors utilize a well-proven ceramic technology
making them an ideal choice across a broad
spectrum of applications.
Product Numbers
Product
Number
Operating
Differential
Pressure
Rating
(psi)
Max.
Differential
Pressure
Between
High &
Low Ports
(psi)
Burst
Pressure
(psi)
QBE3100UD25
0 to 25 72
QBE3100UD50
0 to 50 116
QBE3100UD100
0 to 100 290
540
Pressure Rating
CAUTION:
The maximum manifold pressure rating
is 250 psi.
Exceeding the maximum differential
pressure will damage the sensor.
Warning/Caution Notations
WARNING:
Personal injury/loss of life may
occur if you do not follow the
procedures as specified.
CAUTION:
Equipment damage or loss of
data may occur if you do not
follow the procedures as
specified.
Contents
Sensor
Rubber gasket
Conduit plug with cable gland
90° mounting bracket and mounting screws
Required Tools
Thread Sealant
(2) open-ended wrenches or
(4) crescent wrenches: 1/2”, 5/8", 11/16",
and 9/16”
Small, Phillips screwdriver
Small, flat-blade screwdriver
Installation Time
30 minutes
Prerequisites
Use two male connector compression
fittings with 1/4”-18 NPT threads rated for
system pressure for the HIGH and LOW
pressure ports of the sensor (not included).
Prepare the fittings with Loctite 565 Thread
Sealant or equivalent anaerobic liquid to
prevent leakage.
CAUTION:
Do not use putty, gasket-type
material, or tape.
Installation
Installing the Sensor
1. Assemble compression fittings to the sensor
finger-tight, and then tighten a minimum 2 to 3
turns with 5/8” wrench or to a maximum 25 ft-lbs
(34 Nm) while holding the sensor fitting with the
11/16" wrench. See
Figure 1.
Sensor
Fitting
SEN0642R1
Do Not
Open
Compression Fittings
(Not Included)
Figure 1. Sensor Fitting Location.