User Manual
Table Of Contents
6/6
Smart Infrastructure Pressure sensors QBE2002-P... CE1N1909en
2021-04-07
Internal diagram
MUG
1909G01
(+) (0)( )
BT terminal marking
Color of
core
Meaning
G (+) Brown
Supply voltage
AC 24 V or DC 18...33 V
U
Green
Output signal DC 0...10 V
(signal ground GND)
M (0) White GND
Dimensions
20
10
ca. 87
ca. 108
G1/2
ø 34,5
1909M01
SW 27
1909M02
SW 27
20
10
ø 4,5
57
37,5
21
37
20
5
4,5
M4
Dimensions in mm
( )
QBE2002…
G
1
9
0
7
G
0
2
(+) ( )
BT terminal marking Color of core Meaning
G (+) Brown Supply voltage DC 11...33 V
I
Green Output signal DC 4...20 mA
QBE2102…
QBE2002-P…
QBE2102
-
P…
AQB22.1
( )
Published by:
Siemens Switzerland Ltd.
Smart Infrastructure
International Headquarters
Theilerstrasse 1a
6300 Zug
Switzerland
Tel. +41 58-724 24 24
www.siemens.com/buildingtechnologies
© Siemens Switzerland Ltd 200
5