Disposal
The devices are considered electronics devices for disposal in terms of European
Directive 2012/19/EU and may not be disposed of as domestic waste.
Dispose of the device via the channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.
Technical data
Electrical interface
Power supply
Supply voltage (QBE2002…)Current consumption
Supply voltage (QBE2102…)
Current consumption
with extra-low voltage only (SELV)
AC 24 V ±15%, 50...60 Hz or DC 18...33 V<6 mA
DC 11…33 V
<20 mA
External supply line protection
Fuse slow max. 10 A
or
Circuit breaker max. 13 A
Characteristic B, C, D according to EN 60898
or
Power source with current limitation of
max. 10 A
Output signal QBE2002…
Output signal QBE2102…
DC 0 ...10 V, RLoad >10 k
(not galvanically separated, 3-wire connection,
short-circuit proof and protected against polarity
reversal)
DC 4…20 mA , RLoad Ohm
(not galvanically separated, 2-wire connection,
short-circuit proof and protected against polarity
reversal)
Functional data
Application range refer to "Type summary"
Accuracy:
Total of linearity, hysteresis
and reproducibility
Zero point, Full scale
(FS = Full Scale)
<±0.4 % FS
<±0.6 % FS
Temperature drift:
TC zero point
TC sensitivity
balancing in bar
<±0.04 % FS/K
<±0.015 % FS/K
Response time <5 ms
Nominal pressure
relative pressure as in "Type summary"
(measurement of difference from ambient
pressure)
Max. admissible pressure 2 x scale end value of measuring range (FS)
Rupture pressure 3 x scale end value of measuring range (FS)
Media
Admissible temperature of medium
neutral and slightly corrosive liquids and gases
(suited for use with oil-contacting media)
40... 80 °C
Maintenance maintenance-free
Mounting position Optional
Operating voltage – 11 V
0.02 A