User Manual

11 / 20
Siemens Central apartment unit with consumption data acquisition QAX913 CE1N2740en
Building Technologies 2016-01-30
DHW sensor
Air quality sensor (CO
2
sensor)
Humidity sensor
Outputs
Transmits heat demand (switching)
Transmits heat demand DC 0…10 V
Transmits cooling demand (switching)
Transmits cooling demand DC 0…10 V
Cooling enable
Switching room group pump 1 - 2
Precontroller mixing valve 1 - 2
Step switch 1 to 3 stages
Heat recovery bypass
Enable exhaust hood
Enable cooling unit 1 - 12
Transmits changeover to summer operation
Status output (on / off) for reporting definable events
Window / door state output (on / off) for signaling open windows and doors
DHW charging pump / DHW diverting valve
Electric immersion heater
Switching group relays 1 – 8
Fault outputs 1 - 2
Monitoring state
Status outputs 1 - 4
Water shutoff valve
Gas shutoff valve
The central apartment unit has 8 fault inputs and 2 fault outputs which can be used
either via the universal input / universal output on the QAX913 (locally) or the uni-
versal inputs / universal outputs on the RRV912 / RRV918 heating circuit control-
lers or the RRV934 multicontroller.
Faults of external system components, such as a faulty oil tank level switch, can be
transmitted to the central apartment unit via 8 fault inputs. Each fault input can be
assigned one of the following fault types:
Water leak
Gas leak
CO alarm
Panic
Emergency
Fault 1 - 3
System-internal faults can be transmitted via fault outputs to external components.
The central apartment unit is capable of communicating via a wireless bus
(KNX RF) or a wire-bound bus (KNX TP).
The OCI700 service tool or the OCI702 service interface can be connected to the
service interface (RJ45) located on the underside of the central apartment unit.
Fault inputs / outputs
Communication
Service interface