Operating Instructions

45 / 110
Siemens Synco™ living CE1B2740en
Building Technologies Central apartment unit QAX9x3 13.12.2010
Comfort mode
Precomfort mode
Economy mode
Protection
The optimization time (forward shift) can be limited to a maximum value, sepa-
rately for optimum start and optimum stop control (optimum start control 48
hours / optimum stop control 06.00 hh.mm).
When setting the optimization time to ---- or 00.00, the function is deactivated.
Main menu > Rooms > Room X > Room settings
> OptStartCtrl max:
Factory setting --- (none)
Main menu > Rooms > Room X > Room settings
> OptStopCtrl max:
Factory setting 00.00 (none)
The apartment timer function is ended without optimum start/stop
control.
Room temperature supervision
The controller is capable of continuously monitoring the individual room tem-
peratures. If the room temperature exceeds “Max temp alarm“ (0..35 °C) or
falls below “Min temp alarm“ (0..35 °C), an error message is displayed. Setting
“----“ deactivates temperature supervision of the respective room.
Main menu > Rooms > Room X > Room settings
> Max temp alarm:
Factory setting --- (none)
Main menu > Rooms > Room X > Room settings
> Min temp alarm:
Factory setting --- (none)