Commissioning Instructions

71 / 134
Siemens Synco™ living CE1C2740en
Building Technologies Commissioning the system 13.12.2010
Connect the output for the electric immersion heater
Inform the central apartment unit that you want to use an output to connect an
electric immersion heater:
Main menu > Commissioning > RF connections
> DHW > Electric immersion heater > Connect device:
The following device channels can be connected:
Universal relay output Qx of a multi-controller (see page 65).
Universal relay
output Qx of a heating circuit controller (see page 62).
Connect meteo sensor
Inform the central apartment unit that you want to connect a meteo sensor:
Main menu > Commissioning > RF connections
> Meteo sensor > Connect device:
The QAC910 meteo sensor is automatically switched on as soon as the bat-
teries are inserted.
When switching on (power-up), the battery charge is tested. If charged suffi-
ciently, the green LED is lit for 2 seconds during the test.
If charge is too low for operation, the LED is lit red for 2 seconds –
provided there is enough charge.
After the battery test, the device changes directly to normal operation. The
LED goes out again.
F
LED
2707Z18
Press multifunction button F on the meteo
sensor. The LED lights up in accordance
with the battery charge (green: Bat. ok,
red: Bat not ok). Release the button when
the LED starts blinking.
F = Function button
LED = Light emitting diode
The binding LED on the device blinks green and goes out on successful bind-
ing with the central apartment unit.
To confirm successful connection, the central apartment unit beeps.
The device is now connected and performs normal operation.