Commissioning Instructions

67 / 134
Siemens Synco™ living CE1C2740en
Building Technologies Commissioning the system 13.12.2010
Universal relay output Qx of a heating circuit controller (see page 62).
Universal relay output Qx of a multi-controller (see page 65).
RF adapter plug
KRF960 (see page 72).
Successful connection is display
ed on the central apartment unit and con-
firmed with a beep.
Press the
Menu/ok button to exit the binding process.
Connect room group devices
Inputs and outputs are assigned to the following room group devices:
Mixing valve
Flow sensor
Return sensor
Room group pump
The devices can be connected for room groups 1 and 2.
On the room group devices, the respective input and output functions
must be set to "Via RF", enabling an input or output of a heating cir-
cuit controller or multi-controller to be assigned to them.
Connect output for the mixing valve
Inform the central apartment unit that you want to assign the output to control
a mixing valve of a room group:
Main menu > Commissioning > RF connections > Room groups
> Room group X > Mixing valve > Connect device:
Mixing valves can only be connected via an RRV934 multi-controller.
Mixing valve, flow and return sensor of the same room group must be
connected to the same multi-controller.
The following device channels can be connected:
0..10 V universal output Ux of a multi-controller (see page 65).
3-position output (channel group
Q4/Q5) of a multi-controller (see page 65).
Connect input for flow sensor / return sensor
Inform the central apartment unit that you want to use an input as a flow or re-
turn temperature sensor input:
Main menu > Commissioning > RF connections > Room groups
> Room group X > Flow temperature sensor > Connect device:
Main menu > Commissioning > RF connections > Room groups
> Room group X > Return temperature sensor > Connect device:
The following device channels can be connected:
Universal input Xx of a multi-controller (see page 65).