Commissioning Instructions
57 / 134
Siemens Synco™ living CE1C2740en
Building Technologies Commissioning the system 13.12.2010
Start value
When connecting meters via a pulse input, the meter value must be entered
as start value to match the central apartment unit display to that of the meter.
Entry is in digits without commas. Eight digits are available (see page 54).
For the start value, you can only enter as many decimals as start
value as displayed on the central apartment unit. The decimal places
displayed on the central apartment unit are visible when setting the
unit factor (see page 55).
Example:
Meter display = 2.375 m
3
Unit factor = Liters x 10 =
888888.88 m
3
Start value = 00000237 (without 3
rd
decimal place, as the value on the central
apartment unit only uses 2 decimal places).
Main menu > Commissioning > Extra configuration
> Meter > … > Start value:
Factory setting 00000000
Calibrate date and year
When partially migrating a Synergyr plant, you can enter the date of the last
calibration for each meter.
Main menu > Commissioning > Extra configuration
> Meter > … > Calibration date:
Main menu > Commissioning > Extra configuration
> Meter > … > Calibration year:
Factory setting
Calibration date 1.1
Calibration year 2000
Synergyr meter number
Assign a Synergyr meter number to each meter when partially migrating a
Synergyr plant.
Main menu > Commissioning > Extra configuration
> Meter > … > Synergyr meter no.:
--- No Synergyr meter number assigned (factory setting).
Meter 1 Heat meter in apartment.
Meter 2 Meter connected to the pulse input of the WRV8x or WRI80
to be replaced.
Meter 3 Meter connected to the 1st pulse input of the 1st pulse
adapter AEW2.1 of the apartment.