Commissioning Instructions

55 / 134
Siemens Synco™ living CE1C2740en
Building Technologies Commissioning the system 13.12.2010
Main menu > Commissioning > Extra configuration
> Meter > … > Impulse sensor type:
Reed contact
with namur
Meter is connected via Reed contact with Namur wiring.
Impulse sensor contacts with Namur wiring offer the ad-
vantage of monitoring the meter for interruption or short-
circuit.
Reed contact Meter is connected via Reed contact (factory setting).
Unit factor
The unit for the conversion factor required for correct meter display is set via
the unit factor when connecting the meter via an impulse input.
Setting Central apartment unit display
Wh 88888888 Wh
Wh x 10 888888.88 kWh
Wh x 100 8888888.8 kWh
kWh 88888888 kWh
kWh x 10 888888.88 MWh
kWh x 100 8888888.8 MWh
MWh 88888888 MWh
kJ 88888888 kJ
kJ x 10 888888.88 MJ
kJ x 100 8888888.8 MJ
MJ 88888888 MJ
MJ x 10 888888.88 GJ
MJ x 100 8888888.8 GJ
GJ 88888888 GJ
ml 88888888 ml
ml x 10 888888.88 l
ml x 100 8888888.8 l
Liter 88888888 l
Liter x 10 888888.88 m
3
Liter x 100 8888888.8 m
3
m3 88888888 m
3
No unit
88888888
The setting range for the unit factor is limited to meaningful values
and depends on the meter type or medium.