Commissioning Instructions
49 / 134
Siemens Synco™ living CE1C2740en
Building Technologies Commissioning the system 13.12.2010
Progression of outside temperature
Specify if the progression of the outside temperature (info page) should be
displayed.
Main menu > Commissioning > Basic configuration
> Info pages > Progress OT:
No Do not show info page (factory setting).
Yes Show info page.
Progression of air pressure
Specify if progression of the atmospheric pressure (info page) should be dis-
played.
Main menu > Commissioning > Basic configuration
> Info pages > Progress air press:
No Do not show info page (factory setting).
Yes Show info page.
Consumption data
Specify if consumption data (current meter states for all meters assigned to
the apartment) should be displayed on the info pages. One info page is dis-
played per meter type.
Main menu > Commissioning > Basic configuration
> Info pages > Consumption data:
No Do not show info page (factory setting).
Yes Show info page.
Configure cooling mode
2-pipe heating/cooling system
If, in addition to heating, the plant is used for cooling, communicate it to the
central apartment unit via the following setting:
Main menu > Commissioning > Basic configuration
> Miscellaneous > 2-pipe H/C system:
No No 2-pipe system heating/cooling available
(factory setting).
Yes 2-pipe heating/cooling system available.