Commissioning Instructions

47 / 134
Siemens Synco™ living CE1C2740en
Building Technologies Commissioning the system 13.12.2010
Cooling enable
When the respective output terminal closes, the cooling enable created by the
central apartment unit can be communicated to external components/control-
lers.
Specify if a cooling enable relay is used and how it is controlled.
Main menu > Commissioning > Basic configuration
> Outputs > Cooling enable:
Inactive – cooling enable relay not needed
(factory setting).
Via RF/S-mode Cooling enable state issued via:
Relay output Qx of an RRV91.. heating circuit con-
troller or RRV934 multi-controller.
S-mode object on KNX TP1 *.
Q1 (local) Use relay Q1 of the central apartment unit as a cool-
ing enable relay.
* Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode de-
vices on KNX TP1 via commissioning tool (ETS).
Window/door state
If at least one window/door is open, the respective output terminal is closed.
As a result, an open window/door can be shown via an additional external
component.
Specify if a window/door state output is used and how it is controlled.
Main menu > Commissioning > Basic configuration
> Outputs > Window/door state:
--- Inactive – window/door state not needed
(factory setting).
Via RF/S-mode Window/door state delivered via:
Relay output Qx of an RRV91.. heating circuit con-
troller or RRV934 multi-controller.
S-mode object on KNX TP1 *.
Q1 (local) Relay output Q1 of the central apartment unit used
as a window/door state.
* Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode de-
vices on KNX TP1 via commissioning tool (ETS).
Exhaust hood
To release the exhaust hood, at least one of the windows in the selected
rooms must be open, thus making certain that operation of the exhaust hood
does not produce underpressure in the room.