Commissioning Instructions
39 / 134
Siemens Synco™ living CE1C2740en
Building Technologies Commissioning the system 13.12.2010
Water shutoff valve
Relay output for water shutoff valve is switched over from Off to On when the
corresponding water detector detects water.
Specify if a water shutoff valve is available and how it is controlled.
Main menu > Commissioning > Basic configuration > Supervision
> Water shutoff valve:
--- Inactive – water shutoff valve output not needed
(factory setting).
Via RF Water shutoff valve connected to:
• Relay output Qx of an RRV91.. heating circuit con-
troller or RRV934 multi-controller.
• RF adapter plug KRF960.
• S-mode object on KNX TP1 *.
Q1 (local) Water shutoff valve connected to relay output Q1 of
the central apartment unit.
* Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode de-
vices on KNX TP1 via commissioning tool (ETS).
Gas shutoff valve
Relay output for gas shutoff valve is switched over from Off to On when the
corresponding gas detector detects gas.
Specify if a gas shutoff valve is available and how it is controlled.
Main menu > Commissioning > Basic configuration > Supervision
> Gas shutoff valve:
--- Inactive – gas shutoff valve output not needed
(factory setting).
Via RF Gas shutoff valve connected to:
• Relay output Qx of an RRV91.. heating circuit con-
troller or RRV934 multi-controller.
• RF adapter plug KRF960.
• S-mode object on KNX TP1 *.
Q1 (local) Gas shutoff valve connected to relay output Q1 of
the central apartment unit.
* Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode de-
vices on KNX TP1 via commissioning tool (ETS).