Commissioning Instructions

33 / 134
Siemens Synco™ living CE1C2740en
Building Technologies Commissioning the system 13.12.2010
Heat (inlet) Heat meter installed in flow.
Heat (outlet) Heat meter installed in return. (Factory setting)
Cooling energy
(inlet)
Cooling energy meter installed in flow.
Cooling energy
(outlet)
Cooling energy meter installed in return.
Heat and cooling
energy
Combine heat/cooling energy meter. This setting
makes sense only if an M-bus capable meter is
used.
When using M-bus meters, it is important that the set metering me-
dium agrees with the metering medium sent by the M-bus meter.
Otherwise, the central apartment unit displays error message "Wrong
metering medium".
Configure hot water meter
You can record up to 4 hot water meters with the central apartment unit.
An allocation type and name is assigned to each hot water meter.
Main menu > Commissioning > Basic configuration
> Meter > Hot water > Hot water X > Hot water X:
Main menu > Commissioning > Basic configuration
> Meter > Hot water > Hot water X > Allocation:
A hot water meter is activated as soon as the source is set to unequal "---".
Main menu > Commissioning > Basic configuration
> Meter > Hot water > Hot water X > Source:
Configure cold water meter
You can record up to 4 cold water meters with the central apartment unit.
An allocation type and name is assigned to each cold water meter.
Main menu > Commissioning > Basic configuration
> Meter > Cold water > Cold water X > Cold water X:
Main menu > Commissioning > Basic configuration
> Meter > Cold water > Cold water X > Allocation:
A cold water meter is activated as soon as the source is set to unequal "---".
Main menu > Commissioning > Basic configuration
> Meter > Cold water > Cold water X > Source: