Commissioning Instructions
28 / 134
Siemens Synco™ living CE1C2740en
Building Technologies Commissioning the system 13.12.2010
Configure ventilation
The central apartment unit facilitates control of apartment ventilation via the
multi-controller. For the other settings, see page 50 as well as the operating
instructions in section “Ventilation“.
RRV934 Multi-controller
Q1 – Q3 3-stage step switch of ventilation plant
X1 Indoor air quality sensor
X2 Humidity sensor
ZUL Supply air
ABL Extract air
AUL Outside air
FOL Exhaust air
Function
Tell the central apartment unit about the number of stages (speeds) of the fan
used for ventilation.
Main menu > Commissioning > Basic configuration
> Ventilation > Function:
--- Inactive – no ventilation (factory setting).
1-stage 1-stage ventilation.
2-stage 2-stage ventilation.
3-stage 3-stage ventilation.