Commissioning Instructions
103 / 134
Siemens Synco™ living CE1C2740en
Building Technologies Function settings 13.12.2010
Room group 1:
Factory setting
[Curvepoint 1] outside temp -20 °C
[Curvepoint 1] flow temp min 20 °C
[Curvepoint 2] outside temp 10 °C
[Curvepoint 2] flow temp min 20 °C
Room group 2:
Factory setting
[Curvepoint 1] outside temp -20 °C
[Curvepoint 1] flow temp min 20 °C
[Curvepoint 2] outside temp 10 °C
[Curvepoint 2] flow temp min 20 °C
If the minimum flow temperature heating setpoints at both curve-
points are set to the same value (factory setting), the composite out-
side temperature has no impact on the minimum flow temperature
setpoint.
If the outside temperatures at both curvepoints are set to the same
value, the minimum flow temperature heating setpoint at this com-
posite outside temperature changes abruptly.
If the minimum flow temperature heating setpoints are set differently
and there is no valid outside temperature, the central apartment unit
displays an error message.
Maximum limitation
Maximum limitation limits the flow temperature heating setpoint at the top.
Even if more heat is called for, the temperature level is not exceeded.
Maximum limitation cannot be considered to be a safety function as
required with floor heating systems, for instance.
Main menu > Room groups > Room group X
> Limitations space heating > Flow temp max:
Factory setting 40 °C
Return temperature limitation
Preselect here appropriate setpoints for the type of return temperature limita-
tion selected in the basic configuration under “Configure room groups“ (see
page 24).
Main menu > Room groups > Room group X
> Limitations space heating > Return temp min:
Factory setting ---
Main menu > Room groups > Room group X
> Limitations space heating > Return temp max:
Factory setting ---