Commissioning Instructions
102 / 134
Siemens Synco™ living CE1C2740en
Building Technologies Function settings 13.12.2010
TVL Flow temperature
TVLmax Flow temperature – maximum limitation
TVLmin Flow temperature – minimum limitation
TVLmin1 Flow temperature – minimum limitation (curvepoint 1)
TVLmin2 Flow temperature – minimum limitation (curvepoint 2)
TAgem Composite (effectively acting) outside temperature
TAgem1 Composite outside temperature (curvepoint 1)
TAgem2 Composite outside temperature (curvepoint 2)
Main menu > Room groups > Room group X
> Limitations space heating > Flow temp min
The curvepoints of the minimum flow temperature heating setpoint are set as
follows (example shows curvepoint 1):
Flow tem
p
erature min
When selecting the parameter, the
current setting is displayed. Press the
Menu/ok button to go to the setting
level for curvepoint 1.
Flow tem
p
erature min
Using the arrow buttons, you can set
the composite outside temperature for
curvepoint 1. Close the entry by
pressing the
Menu/ok button.
Flow tem
p
erature min
Set the minimum flow temperature
that must not be exceeded at that
composite outside temperature.
Close the entry by pressing the
Menu/ok button.
Flow tem
p
erature min
The settings are adopted and the dis-
play shows the resulting graph.
Use the
arrow button to go to the set-
ting for curvepoint 2. The setting pro-
cedure is the same as that with
curvepoint 1.