User Manual
42 / 100
Siemens Synco™ living Operating instructions CE1B2707en
Building Technologies Central apartment unit QAX910 23.08.2008
Room number 7 8 9 10 11 12
Room name
Factory setting ---- ---- ---- ---- ---- ----
Max temp. alarm
Min temp. alarm
Window airing function
As soon as the central apartment unit detects an open window, the window
airing function is activated in the corresponding room. In that case, the radia-
tor control valve is limited to its current travel, even if the room temperature
drops.
If the window remains open after the set window airing hold time, the room
operating mode is lowered to Protection mode.
The window airing function is aborted as soon as all window contacts in the
respective room have closed again
F Window (0 = all closed, 1 = min one open)
R Room control
RB Control mode
V Hold valve position
SB Protection
t Time
The desired window airing hold time (00.00..06.00 hh.mm) can be defined for
each room.
Main menu > Rooms > Room X > Room settings
> Window airing:
Setting “00.00“ deactivates the window airing function.
The window contacts do not influence room control.
Room number 1 2 3 4 5 6
Room name
Factory setting 00.30 00.30 00.30 00.30 00.30 00.30
Setting
Room number 7 8 9 10 11 12
Room name
Factory setting 00.30 00.30 00.30 00.30 00.30 00.30
Setting