User Manual
41 / 100
Siemens Synco™ living Operating instructions CE1B2707en
Building Technologies Central apartment unit QAX910 23.08.2008
Optimum start / stop control acts between all operating levels, except when
switching between Precomfort and Comfort:
Comfort mode
Precomfort mode
Economy mode
Protection
The optimization time (forward shift) can be limited to a maximum value,
separately for optimum start and optimum stop control (optimum start control
48 hours / optimum stop control 06.00 hh.mm).
When setting the optimization time to ---- or 00.00, the function is deactivated.
Main menu > Rooms > Room X > Room settings
> OptStartCtrl max:
Main menu > Rooms > Room X > Room settings
> OptStopCtrl max:
Room number 1 2 3 4 5 6
Room name
Factory setting ---- ---- ---- ---- ---- ----
Opt start
Opt stop
Room number 7 8 9 10 11 12
Room name
Factory setting ---- ---- ---- ---- ---- ----
Opt start
Opt stop
Room temperature supervision
The controller is capable of continuously monitoring the individual room tem-
peratures. If the room temperature exceeds “Max temp alarm“ (0..35 °C) or
falls below “Min temp alarm“ (0..35 °C), an error message is displayed. Setting
“----“ deactivates temperature supervision of the respective room.
Main menu > Rooms > Room X > Room settings
> Max temp alarm:
Main menu > Rooms > Room X > Room settings
> Min temp alarm:
Room number 1 2 3 4 5 6
Room name
Factory setting ---- ---- ---- ---- ---- ----
Max temp. alarm
Min temp. alarm