Technical data
Operating voltage AC 230 V (± 10%)
Frequency
50 Hz
Power consumption Max. 7 VA
Fusing of supply line
10 A
Reserve of clock
Typically 72 hours
Frequency 868.3 MHz (bidirectional)
Range
Typically 30 m in buildings
Protocol KNX RF-compatible
Bus protocol / type KNX TP1
Bus power supply Simplified bus power supply, 12.5 mA; bus
power supply may only be switched on for
operating an OZW771
Service interface RJ45 socket on underside of housing
Fully graphic backlit display (white background)
Type
LG-Ni1000 resistor, on / off
Quantity 1
Measuring range 0…120 °C
Copper cable 0.6 mm dia.
Copper cable 1 mm
2
Copper cable 1.5 mm
2
Max. 20 m
Max. 80 m
Max. 120 m
Type
NO contact AC 24…230 V,
AC 0.02…2 (2) A
Quantity 1
Screw terminals for Max. 1.5 mm
2
conformity to
EMC directive
- Immunity, Emissions
Low-voltage directive
- Electrical safety
RTTE (Radio & Telecom. Equipment)
- Wireless communication
2004/108/EC
- EN 60730-1, EN 50090-2-2
2006/95/EC
- EN 60730-1, EN 50090-2-2
1999/5/EC
- EN 300220-2, EN 301489-1, EN 301489-3
Environmental product declaration
CE1E2740en provides information on
environmentally compatible product de-
sign and assessment (RoHS compliance,
composition of substances, packaging,
environmental benefit and disposal)
ISO 14001 (Environment)
ISO 9001 (Quality)
SN 36350 (Environmentally compatible
products)
2002/95/EC (RoHS)
Safety class II to EN 60730
Degree of protection of housing IP20D to EN 60529
Degree of pollution 2 to EN 60730
Refer to “Dimensions“
Unit complete with enclosures 0.857 kg
Plastic ASA+PC
White NCS S 0502-G
Power supply
RF
Wired communication
Display
Universal input
Permissible cable
length to sensor or
external switch
Relay output
Electrical connections
Standards
Environmental
compatibility
Protection
Dimensions
Weight
Housing material
Housing color