User Manual

99 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Function settings 23.08.2008
Integral action time Tn
You can set the primary controller’s integral action time Tn for each room
group depending on demand (0..600 s).
Main menu > Room groups > Room group X
> Primary controller > Int action time Tn:
Room group 1 Room group 2
Factory setting 60 s 60 s
Your setting
…………… s
…………… s
Ventilation
Indoor air quality control
The indoor air quality controller calculates a positioning signal based on the
current setpoint (in accordance with the ventilation level) and the current
indoor air quality.
From this, the linear step selector derives the ventilation stage presently re-
quired.
The ppm level of indoor air quality is displayed on the central apartment unit.
Indoor air quality at 0 V / 10 V
To provide indoor air quality control, an indoor air quality sensor (DC 0..10 V)
must be connected.
The indoor air quality sensor must be located in the room itself, thus
ensuring that air also circulates around the sensor when the ventilation
system is off. Do not install the sensor in the extract air duct.
The ppm level for 0 V and 10 V (0..2000 ppm) can be set.
Main menu > Ventilation > IAQ controller > IAQ at 0 V:
Factory setting 0 ppm
Your setting
Main menu > Ventilation > IAQ controller > IAQ at 10 V:
Factory setting 2000 ppm
Your setting