User Manual
95 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Function settings 23.08.2008
TVL Flow temperature
TVLmax Flow temperature – maximum limitation
TVLmin Flow temperature – minimum limitation
TVLmin1 Flow temperature – minimum limitation (curvepoint 1)
TVLmin2 Flow temperature – minimum limitation (curvepoint 2)
TAgem Composite (effectively acting) outside temperature
TAgem1 Composite outside temperature (curvepoint 1)
TAgem2 Composite outside temperature (curvepoint 2)
Main menu > Room groups > Room group X
> Limitations > Flow temperature min…
The curvepoints of the minimum flow temperature setpoint are set as follows
(example shows curvepoint 1):
Flow tem
p
erature min
When selecting the parameter,
the display with the current setting
appears. Press the Menu/ ok
button to go to the setting level for
curvepoint 1.
Flow tem
p
erature min
Now, using the arrow buttons,
you can set the composite outside
temperature for curvepoint 1.
Finish the entry by pressing the
Menu/ok button.
Flow tem
p
erature min
Set the minimum flow temperature
which shall not be crossed at that
composite outside temperature.
Finish the entry by pressing the
Menu/ok button.
Flow tem
p
erature min
The settings are adopted and the
display shows the resulting graph.
Use the arrow button to go to the
setting for curvepoint 2. The
setting procedure is the same as
that with curvepoint 1.