User Manual
93 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Function settings 23.08.2008
Neutral zone
For rooms using 3-position actuators, the room controller’s neutral zone
(0..20 K) can be set for every room. For your guidance, refer to the default
settings:
Room type Guide value neutral zone
Radiator heating slow 0.1 K
Radiator heating fast 0.1 K
Floor heating slow 0.1 K
Floor heating fast 0.1 K
Main menu > Rooms > Room X > Room controller > Neutral zone:
Room number 1 2 3 4 5 6
Room name
Factory setting 0.1 K 0.1 K 0.1 K 0.1 K 0.1 K 0.1 K
Setting Neut.
Room number 7 8 9 10 11 12
Room name
Factory setting 0.1 K 0.1 K 0.1 K 0.1 K 0.1 K 0.1 K
Setting Neut.
Switching differential 2-position
For rooms using 2-position actuators, the room controller’s switching differen-
tial (0..20 K) can be set for every room. For your guidance, refer to the default
settings:
Room type Guide value switching differential
Radiator heating slow 0.8 K
Radiator heating fast 0.8 K
Floor heating slow 0.8 K
Floor heating fast 0.8 K
Main menu > Rooms > Room X
> Room controller > Switching diff 2-pos:
Room number 1 2 3 4 5 6
Room name
Factory setting 0.8 K 0.8 K 0.8 K 0.8 K 0.8 K 0.8 K
Setting SD
Room number 7 8 9 10 11 12
Room name
Factory setting 0.8 K 0.8 K 0.8 K 0.8 K 0.8 K 0.8 K
Setting SD