User Manual

92 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Function settings 23.08.2008
Integral action time Tn
The room controller’s integral action time can be set for every room. For your
guidance, refer to the default settings:
Room type Guide value Tn
Radiator heating slow 5,400 s
Radiator heating fast 3,600 s
Floor heating slow 7,200 s
Floor heating fast 5,400 s
Main menu > Rooms > Room X > Room controller > Int action time Tn:
Room number 1 2 3 4 5 6
Room name
Factory setting 5,400 s 5,400 s 5,400 s 5,400 s 5,400 s 5,400 s
Setting Tn
Room number 7 8 9 10 11 12
Room name
Factory setting 5,400 s 5,400 s 5,400 s 5,400 s 5,400 s 5,400 s
Setting Tn
Derivative action time Tv
The room controller’s derivative action time can be set for every room. For
your guidance, refer to the default settings:
Room type Guide value Tv
Radiator heating slow 450 s
Radiator heating fast 540 s
Floor heating slow 540 s
Floor heating fast 540 s
Main menu > Rooms > Room X > Room controller > Der action time Tv:
Room number 1 2 3 4 5 6
Room name
Factory setting 450 s 450 s 450 s 450 s 450 s 450 s
Setting Tv
Room number 7 8 9 10 11 12
Room name
Factory setting 450 s 450 s 450 s 450 s 450 s 450 s
Setting Tv