User Manual

91 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Function settings 23.08.2008
even if the room temperature is sufficiently high. It is accepted that in such
cases the room might get overheated.
Main menu > Rooms > Room X > Room settings > Min valve pos comf:
Factory setting 0%
Your setting
H/C changeover locking time
Changeover locking time prevents heating mode from changing to cooling
mode (and vice versa) too quickly and too frequently.
This means that when changing over, heating or cooling mode is disabled.
They are enabled again only when the changeover locking time has elapsed.
Main menu > Rooms > Room X
> Room settings > H/C changeover lock:
Factory setting 00:00
Your setting
……… mm:ss
Room controller settings
These settings are displayed only when a user-defined heating type
has been set (refer to “Configure rooms“, refer to page 18).
P-band Xp
The room controller’s P-band can be set for every room to suit individual
needs. For your guidance, refer to the default settings:
Room type Guide value Xp
Radiator heating slow 2 K
Radiator heating fast 2 K
Floor heating slow 2 K
Floor heating fast 2 K
Main menu > Rooms > Room X > Room controller > P-band Xp:
Room number 1 2 3 4 5 6
Room name
Factory setting 2 K 2 K 2 K 2 K 2 K 2 K
Setting Xp
Room number 7 8 9 10 11 12
Room name
Factory setting 2 K 2 K 2 K 2 K 2 K 2 K
Setting Xp