Building Technologies Function settings 23.08.2008
Economy increase
The Economy room setpoint for heating all rooms is raised depending on the
composite outside temperature. The increase at low outside temperatures
(e.g. end point -15 °C) is greater and negated at higher outside temperatures
(e.g. starting point -5 °C).
This way, long heating up times when changing from Economy to Precomfort
or Comfort setpoint can be prevented at low outside temperatures.
In the case of night setback to Economy setpoint, this function leads to outside
temperature-compensated night setback.
If the setting is made such that start and end point coincide, the function is
deactivated.
An Economy setpoint raised through Economy increase is displayed on the
central apartment unit.
If there is no valid outside temperature when the ”Economy increase”
function is active, the central apartment unit displays an error mes-
sage.
Main menu > Apartment > Settings > Eco incr start point:
Main menu > Apartment > Settings > Eco incr end point:
Starting point End point
Factory setting 0 °C 0 °C
Your setting
……..… °C
……..… °C
Rooms
Room temperature rise
During optimum start control, the central apartment unit ascertains the room
temperature rise (min/K) of the respective room and takes it into account the
next time optimum start control is performed. The value calculated last can be
viewed via an operating line and can be changed, if required:
Main menu > Rooms > Room X > Room settings > Room temp rise:
Proportion room unit
If a QAW910 room unit and 1 or 2 QAA910 room temperature sensors are
connected to the same room, the room unit’s weighting (0..100%) with regard
to room temperature averaging can be set.
If 1 room unit and 1 room temperature sensor are used, the actual value of the
average room temperature is determined based on the percentage proportion
set.