User Manual
86 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Commissioning the system 23.08.2008
Set the outside temperature zone (1..31) and the heat distribution zone (1..31)
and the refrigeration distribution zone (1..31) where the central apartment unit
is located.
When using setting "---", no data of the respective distribution zone is
sent or received via bus.
Main menu > Commissioning > Bus communication
> Distribution zones > Outside temp zone:
Main menu > Commissioning > Bus communication
> Distribution zones > Heat distr zone:
Main menu > Commissioning > Bus communication
> Distribution zones > Refrig distr zone:
Distribution zone Factory setting Your setting
Outside temperature and atmospheric
pressure zone
---
Heat distribution zone 1
Refrigeration distribution zone 1
The zone settings must be unambiguous. For example, only one
outside sensor may have outside temperature zone 1 assigned.
Setting “Refrigeration distribution zone“ is visible only when, in the
basic configuration, ”Yes” was selected with parameter ”2-pipe system
heating / cooling“.
Setting the refrigeration distribution zone enables the central apart-
ment unit to respond to H/C changeover forwarded by a refrigeration
source.
Quitting the “Commissioning“ menu
On completion of commissioning, press the Esc button to quit the “Commis-
sioning” menu. The plant is still out of operation.
When you confirm this message by
pressing the Menu/ok button, the
plant is put into operation according
to the new settings and the display
returns to the ”Main menu”.
This message is displayed if invalid
settings have been made. Press the
Esc or Menu/ok button to return to
the ”Commissioning” menu. The plant
remains out of operation.
Caution!
Plant starts
Caution!
Invalid settings
Start not possible