User Manual
84 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Commissioning the system 23.08.2008
Clock time operation
When using setting “Autonomous“, the device does not receive or send the
time of day. If the system is to use a common time of day, one of the devices
must be defined as the clock time master and the others as slaves.
Main menu > Commissioning > Bus communication
> Time of day/date > Clock time op:
Factory setting Autonomous
Your setting Autonomous
Slave
Master
Ensure that only one device in the system is defined as the clock time
master.
Remote setting clock slave
Function “Remote setting clock slave = Yes“ enables the user to also set the
time of day and the date on a clock time slave.
The new values are transmitted to the clock time master via the Konnex bus.
The clock time master distributes the new time to all bus users. Hence, for the
plant user, operation is the same as that on the clock time master.
Main menu > Commissioning > Bus communication
> Time of day/date > Rem set clock slave:
Factory setting Yes
Your setting Yes
No
Calendar zone (holidays and special days)
When using calendar zone setting “Autonomous“, the device does not receive
or send calendar dates. If several devices in the system are to use a common
calendar, holiday / special day operation must be set to ”Master” on every
such device, and to ”Slave” on the other devices.
Main menu > Commissioning > Bus communication
> Holidays/special days > Hol/spec day op:
Factory setting Autonomous
Your setting Autonomous
Slave
Master
In addition, with master / slave operation, set the required holiday / special day
zone (1..31).